ANTSPACE HW5
$75,200
| Function: | Hydro-cooling container |
| Specifications: | 1Set | 1200KW | 210 Rack Space |
Description
Specifications
| Product Overview | Value |
| Model | ANTSPACE HW5 |
| Version | V1 |
| Dimensions (l*w*h), mm | 12192×2438×2896 |
| Miner capacity | 210 units S23 Hyd. & S21 Hyd. & S19 Hyd. series miner |
| PUE@25℃ ambient temperature | 1.017 |
| Container certification | CSC |
| Safety certification | NFPA 79:2021 UL 508A:2018 R8.21 CSA C22.2 No. 14-18 ANSI/ISO 12100:2012 IEC 60204 Ed 5.1 2009 |
| Input voltage and frequency | 400V±5% 50/60Hz |
| Detailed Characteristics | Value |
| Shipping weight, T | 14 |
| Operating weight, T | 24 |
| Main switch of power distribution cabinets, A | 1200*2 |
| Rated current, A | ≤986*2 |
| Rated Current per Miner, A | ≤10 |
| Normal power, kW | 1200 |
| Inlet cable(1-1) | The inlet copper cables can withstand voltage of above 600V, with the following requirements: L1 single core cable 600kcMil(300mm²)x6 L2 single core cable 600kcMil(300mm²)x6 L3 single core cable 600kcMil(300mm²)x6 N Single-core cable 600kcMil(300mm²)x4 PE single-core cable 500kcMil(240mm²)x2 |
| Flow rate, m³/h | ≥85 |
| Quantity of ANTSPACE powered by one 2500kVA Transformer | 2 |
| ANTSPACE HW5 Dry-Wet Tower Cooling Module | |
| Heat Dissipation Capacity, kW | 1200 |
| Outlet Temperature @ 28℃ Wet Bulb Temperature, ˚C | 35 |
| Operating Power, kW | ≤15~29 |
| Water supply pipe Interface | DN40(Internal thread) |
| Drain Pipe Interface | DN65(Internal thread) |
| Noise level @25℃, 15m, dBA | 70 |
| Water Consumption, m³/h | 0.7~1.3 |
| Inner Coolant Usage, m³ | 1.6 |
Additional information
| Weight | 14000 kg |
|---|---|
| Dimensions | 12192 × 2438 × 2896 mm |
| Condition | NEW |