Avalon Immersion Cooling Mining Box 40ft
$146,100
| Function: | Immersion-cooling container |
| Specifications: | 1Set | 1200KW | 144 Rack Space |
Modular design.
Electrical safety compliance.
Factory prefabricated and integrated delivery.
Excellent Overclocking Capabilities.
Extra Large Capacity of Tank.
Multiple Cooling Solutions.
Description
Specifications
| Introduction | |
| Version | OA V5.0.40.3.086 |
| Cooling Method | Immersion Cooling |
| Miner Capacity | 144 units |
| Container Certification | Classification Society |
| Safety Certification | IEC |
| Input Voltage and Frequency | 380V~415V, AC, 50Hz (A, B, C, N, PE) |
| Basic Capacity | |
| Power Capacity for Miners | 1200 kW@25℃ |
| Maximum Power@Single Position | 6.0 kW |
| PUE | ≤1.08 |
| Basic Configuration | |
| Critical Equipment | Configuration or Dimensions |
| Tank Container | LxWxH:12192x2438x2896 mm |
| Cooling Container | LxWxH:12192x2438x2896 mm |
| Tank | 18 units@single Tank |
| Power Distribution Cabinet | 1250A x 2 sets |
| PDU** | 250A,30A x 18 sets |
| Switch | Aggregation and terminal switches |
| Coolant Pump | Customized pumps |
| Cooling Unit | 1000kW@25℃ |
| Control System | PLC, monitoring, start-stop, alarming |
| Others | Integrated smoke sensor, temperature sensor, ventilator |
| Conditions of Carriage | |
| Tank Container | Shipping Weight (T)≤15 Operating Weight (T)≤25 |
| Cooling Container | Shipping Weight (T)≤12 Operating Weight (T)≤20 |
| Noise | |
| Sound Pressure LpA (10m) | ≤70 dB(A) |
| Key materials | |
| Dry Cooler | Copper tube Aluminum fins |
| Pipe | SS304 |
Additional information
| Weight | 15000 kg |
|---|---|
| Dimensions | 12192 × 2438 × 2896 mm |
| Condition | NEW |